Skip to content
Akan Industrial and Automation

Honeywell – Scame Sistemi

Honeywell Scame HS81 I/O Cards and Modules

HS81 I/O cards for addressable and conventional fire detection loops, alarm outputs, extinguishing control (EN 12094-1), safety bus remote I/O and SSP loop modules.

  • Expansion of HS81 fire and gas panels
  • Addressable and conventional fire detection loops
  • Extinguishing (suppression) release control
  • Remote I/O across large plant areas
Honeywell Scame HS81 I/O Cards and Modules

HS81 I/O cards are the plug-in input and output cards of the Honeywell Scame HS81 industrial fire and gas system. They connect addressable and conventional detection loops, alarm sounders and actuators, extinguishing release logic and distributed remote I/O to the HS81 panel. Akan Industrial and Automation supplies HS81 cards in Türkiye for new systems and for expansions of existing panels.

HS81 card overview

Card Function Key data
Analog addressable device control card Loop card for Apollo Discovery / XP95 detectors, call points, sounders/beacons and I/O modules 127 multichannel addresses; loop up to 1500 m; dynamic smoke detector thresholds; XPander wireless support; hot-swappable
F7002 analog addressable device control card Loop card for Hochiki ESP smoke, heat and multi-sensor detectors, call points and control modules Up to 127 addresses × 3 channels; loop up to 1500 m; HIGH/MEDIUM/LOW sensitivity; fire detection only
F3002 8-input card Eight conventional (non-addressable) detection lines Two alarm thresholds per line; automatic alarm verification; line test every 30 s; suitable up to SIL 3 (IEC 61508); cross-line logic for NFPA extinguishing; intrinsically safe systems
F5003 alarm control card Eight monitored output lines for sounders and actuators 8 × 500 mA; polarity-reversal supervision; steady or pulsing; NFPA-compliant systems
F6001 control card Extinguishing control logic (virtual I/O) 4 virtual inputs, 10 virtual outputs; EN 12094-1; 0–60 s delay; supports SIL 2 and SIL 3 (IEC 61508) extinguishing systems
F7011 safety bus system module Remote I/O over an enhanced-safety CAN ring Up to 64 remote modules per loop; mono or duplex control cards; redundant network; weatherproof and explosion-proof module housings
Loop control module Loop for SSP addressable modules Up to 127 modules; technological signals only – not for fire detectors

All cards use SMD multilayer technology, FPGA-based communication, microcontroller logic and front plug-in mounting in 19” racks with locking screws.

Why choose Akan?

Akan selects the card mix for your detection and suppression philosophy, configures the panel and commissions the system. See the HS81 fire and gas panels and HS81 power modules.

Frequently asked questions

Which detector protocols do HS81 loop cards support?

The analog addressable device control card supports Apollo Discovery and XP95; the F7002 supports Hochiki ESP; the loop control module supports SSP for technological signals.

How long can an HS81 addressable loop be?

The farthest point on the loop can be up to 1500 m from the panel.

Which card handles extinguishing release?

The F6001 control card manages extinguishing logic using the I/O of other cards and makes the S81 system compliant with EN 12094-1, with a configurable 0–60 s release delay.

How can field I/O be distributed over a large site?

The F7011 safety bus connects up to 64 addressable remote modules per loop over a redundant CAN-based ring; modules are available in weatherproof and explosion-proof housings.

Request a quote

Tell us about your application and our engineers will get back to you within one business day.

Search